This installation was on a 4-story home, and the tech had not yet gone to the basement to troubleshoot the “infinity” water source heat pump, as he was told he by the homeowner. He was in the attic at the infinity furnace above the 4th floor. He was getting his dcv in the proper range on his A and B green plug on the air handler, 3 to 4 vdc. His indoor board ohm reading was in range, 28k to 32 k. The tech ohmed out the A and B thermostat wires on the water source heat pump from the upstairs. His ohm reading was not in range of a normal infinity board. His reading was around 64.4k. The tech then made the long walk to the basement where the “geothermal heat pump” was located. Bingo. 

Now get out there and organize some zone wiring!

Zone equipment would be identified as indoor unit- blue black/ outdoor unit-blue green:

Two wire bundles with colored insulated strands and blue tape ties on brown cable ends.
Picture of Anthony Coker

Anthony Coker

Technical Services Manager North Georgia District

November 17, 2022

Cleaning Coils

Fall is the time for the leaves to fall and with the mixture of rain and wind tends to stir up debris that can cause your outdoor coil to get dirty along with all the natural elements that cause deposits to attach to the coils. With that said, we want to make sure that we are cleaning the coils properly and to Carrier specifications to extend the coil lives longer.


The most important thing to remember is safety first. Always wear the proper PPE (Personal Protection Equipment) when working with chemicals and always be aware of the SDS (Safety Data Sheets) as to be aware of what steps to take if ingested, inhaled, or if it gets on your skin and the things to do for protection along with precautions that you might be or not be aware of!


Now that we are past all the boring stuff, let us get down to the good stuff!


Coil cleaners come in a variety of strengths and concentrations that need to be taken seriously. An example would be: if you washed your clothes with pure bleach what would happen? Nothing good I can guarantee that! You will want to read the labels on the containers to make sure you have the properly mixed solution. You will have a label on every container size that tells you the proper ratio for mixing the cleaners with water to dilute it to the specified ratio required to do the best and safest cleaning job possible. If you go over it, it can do more damage than good by eating or breaking down the elements that make up the coil. Too little and you don’t have a clean coil.


Just a few part numbers of the variety of coil cleaners available!


P902-0101, P902-0301, P902-1001, P902-1801



Below are photos of coil cleaners and their labels so that you can see the mixing ratios and instructions of use.

Triple-Clean cleaning solution bottle with orange label on a store shelf
Label on a pink plastic bucket sitting on a store shelf.
Bottle of orange condenser cleaner on a store shelf, labeled
White chemical jug on a store shelf with hazard label and barcode
Green Totaline environmentally sound coil cleaner jug with a teal label on a store shelf
Close-up of a teal Totaline air conditioner cleaner can with product label text.

When you use any coil cleaner, you should clean out all debris from cabinet before using so that it can drain properly. Proper drainage can increase efficiency. Rinse thoroughly and always use safety!

249 VAN Launch Kit 249 VAN Consumer Brochure Smart Thermostat Sell Sheet 249 VAN Launch Kit

Unlock the Full Potential

View Quick Start Guide

This installation was on a 4-story home, and the tech had not yet gone to the basement to troubleshoot the “infinity” water source heat pump, as he was told he by the homeowner. He was in the attic at the infinity furnace above the 4th floor. He was getting his dcv in the proper range on his A and B green plug on the air handler, 3 to 4 vdc. His indoor board ohm reading was in range, 28k to 32 k. The tech ohmed out the A and B thermostat wires on the water source heat pump from the upstairs. His ohm reading was not in range of a normal infinity board. His reading was around 64.4k. The tech then made the long walk to the basement where the “geothermal heat pump” was located. Bingo. 


More to Explore

Family relaxing in a bright living room, parents on a gray couch with laptops while children play nearby
By Austin Sims August 4, 2026
At Mingledorff's we understand your business. We are your #1 HVAC and plumbing distributor choice. Trust our experience. Contact us today!
Mingledorffs
By Jenny Reed August 4, 2026
At Mingledorff's we understand your business. We are your #1 HVAC and plumbing distributor. Trust our experience. Contact us today!
Bright hobby shop with display cases, counter, and model kits; a few people stand near the back.
By Jenny Reed August 3, 2026
At Mingledorff's we understand your business. We are your #1 HVAC and plumbing distributor. Trust our experience. Contact us today!
Bright hobby shop interior with display cases, model kits, and a counter with two people inside.
By Jenny Reed August 3, 2026
At Mingledorff's we understand your business. We are your #1 HVAC and plumbing distributor. Trust our experience. Contact us today!

Heat Pump

Keep up with the latest HVAC news from Mingledorff’s Inc.